💨 Steam Humidifier & Absorption

Calculate steam injection rates (kg/h), boiler power, and non-wetting absorption distance (m) to prevent duct condensation and mold growth per ASHRAE 62.1.

⚡ Fortran 90 Engine Double Precision (IEEE 754) ✓ ISO / ASME Validated
📊 Solver Telemetry ● ACTIVE
👁️ Consultations 24
⚡ Calculs faits 21
💾 Téléchargements 240 📦 Code Fortran 4.4 KB
📅 Mise en service Jun 2026
⏱️ Latence < 1 ms
⚡ Outils & Rapports :
💾 Télécharger Fortran 90

💨 AHU Steam Dispersion Manifold & Non-Wetting Absorption Plume

Real-time visual simulation of steam micro-jet discharge & absorption distance envelope (D_abs)

📝 Configuration & Presets

🏢 Office Winter (20% -> 45%) 🏥 Hospital ICU (6-Tube Grid) 🧪 Single Wand Tube (15% -> 40%) 📰 Printing Press (60% RH)
💨 AHU Airflow & Duct Cross-Section
💧 Relative Humidity Targets & Manifold
Multiple tubes drastically shorten D_abs
ASHRAE 62.1 Formulations:
• Steam Rate: ṁsteam = ṁair · (w₂ − w₁) × 3600 [kg/h]
• Absorption Distance: Dabs ∝ (1 / Ntubes0.75) · vair · [ (RH₂ − RH₁) / (100 − RH₂) ]0.65 [m]
• Electric Power: P = ṁsteam · hfg / 3600 [kW]

📊 Humidification Results

📊 Output Summary
💾 Fortran Source

Required Steam Injection Rate
steam = 15.32 kg/h (33.8 lb/h)
Moisture Gain: Δw = 3.63 g/kg (15% → 40% RH)
Dabs = 1.70 m
Non-Wetting Absorption Distance 1.70 meters 1 tube(s) @ 4.1 m/s
Electric Boiler Power Required 10.85 kW 37017 BTU/h
Air Velocity in Duct (vair) 4.05 m/s 797 FPM
Specific Humidity Ratio (w₂) 5.79 g/kg Entering w₁ = 2.16 g/kg

📈 Steam Output Rate (kg/h) vs Target RH (%)

📉 Absorption Distance (m) vs Number of Manifold Tubes

=================================================================
 THERMOFLUIDCALC — STEAM HUMIDIFIER & ABSORPTION REPORT
=================================================================
Case Title                 : Small Commercial Single Dispersion Tube Humidifier
Air Volume Flow Rate (Q)   : 3,500.0 m3/h (2,060 CFM)
Duct Cross-Section (W x H) : 600 mm x 400 mm (v = 4.05 m/s)
Entering / Target RH       : 15.0 % -> 40.0 % RH (at 20.0 °C DB)
Dispersion Manifold Tubes  : 1 tube(s)
-----------------------------------------------------------------
STEAM INJECTION CAPACITY   : 15.32 kg/h (33.77 lb/h)
NON-WETTING ABSORPTION DIST: 1.70 meters (5.6 feet)
Electric Boiler Power Draw : 10.85 kW (37017 BTU/h)
Entering Humidity Ratio w1 : 2.16 g/kg
Target Leaving Ratio w2    : 5.79 g/kg (Δw = +3.63 g/kg)
=================================================================

📘 Calculation Methodology & ASHRAE 62.1 Standards

Non-Wetting Absorption Distance

Visible steam plumes must fully absorb before reaching duct obstructions (elbows, filters, silencers) to prevent stagnant liquid pooling and biological mold growth:

Dabs ∝ (1 / Ntubes0.75) · vair · [ ΔRH / (100 − RH₂) ]0.65

Multi-Tube Rapid Dispersion Grids

Distributing steam across multiple vertical headers with engineered precision nozzles shortens absorption distance by up to 75% compared to single-wand injection.

Key Engineering Assumptions

  • Atmospheric dry saturated steam at $100^\circ\text{C}$ ($h_{fg} = 2257\,\text{kJ/kg}$).
  • Electric resistive or electrode boiler thermal efficiency $\eta \approx 95\%$.
  • Isothermal humidification process along dry bulb lines.