💨 Steam Humidifier & Absorption
Calculate steam injection rates (kg/h), boiler power, and non-wetting absorption distance (m) to prevent duct condensation and mold growth per ASHRAE 62.1.
⚡ Fortran 90 Engine
Double Precision (IEEE 754)
✓ ISO / ASME Validated
📊 Solver Telemetry
● ACTIVE
👁️ Consultations
24
⚡ Calculs faits
21
💾 Téléchargements
240
📦 Code Fortran
4.4 KB
📅 Mise en service
Jun 2026
⏱️ Latence
< 1 ms
💨 AHU Steam Dispersion Manifold & Non-Wetting Absorption Plume
Real-time visual simulation of steam micro-jet discharge & absorption distance envelope (D_abs)📝 Configuration & Presets
🏢 Office Winter (20% -> 45%)
🏥 Hospital ICU (6-Tube Grid)
🧪 Single Wand Tube (15% -> 40%)
📰 Printing Press (60% RH)
ASHRAE 62.1 Formulations:
• Steam Rate: ṁsteam = ṁair · (w₂ − w₁) × 3600 [kg/h]
• Absorption Distance: Dabs ∝ (1 / Ntubes0.75) · vair · [ (RH₂ − RH₁) / (100 − RH₂) ]0.65 [m]
• Electric Power: P = ṁsteam · hfg / 3600 [kW]
• Steam Rate: ṁsteam = ṁair · (w₂ − w₁) × 3600 [kg/h]
• Absorption Distance: Dabs ∝ (1 / Ntubes0.75) · vair · [ (RH₂ − RH₁) / (100 − RH₂) ]0.65 [m]
• Electric Power: P = ṁsteam · hfg / 3600 [kW]
📊 Humidification Results
📊 Output Summary
Required Steam Injection Rate
ṁsteam = 37.23 kg/h (82.1 lb/h)
Moisture Gain: Δw = 3.88 g/kg (20% → 45% RH)
Dabs = 0.73 m
Non-Wetting Absorption Distance
0.73 meters
4 tube(s) @ 4.6 m/s
Electric Boiler Power Required
26.37 kW
89982 BTU/h
Air Velocity in Duct (vair)
4.63 m/s
911 FPM
Specific Humidity Ratio (w₂)
6.95 g/kg
Entering w₁ = 3.07 g/kg
📈 Steam Output Rate (kg/h) vs Target RH (%)
📉 Absorption Distance (m) vs Number of Manifold Tubes
================================================================= THERMOFLUIDCALC — STEAM HUMIDIFIER & ABSORPTION REPORT ================================================================= Case Title : Commercial Office AHU Winter Humidification (4-Tube Rapid Grid) Air Volume Flow Rate (Q) : 8,000.0 m3/h (4,709 CFM) Duct Cross-Section (W x H) : 800 mm x 600 mm (v = 4.63 m/s) Entering / Target RH : 20.0 % -> 45.0 % RH (at 21.0 °C DB) Dispersion Manifold Tubes : 4 tube(s) ----------------------------------------------------------------- STEAM INJECTION CAPACITY : 37.23 kg/h (82.08 lb/h) NON-WETTING ABSORPTION DIST: 0.73 meters (2.4 feet) Electric Boiler Power Draw : 26.37 kW (89982 BTU/h) Entering Humidity Ratio w1 : 3.07 g/kg Target Leaving Ratio w2 : 6.95 g/kg (Δw = +3.88 g/kg) =================================================================
📘 Calculation Methodology & ASHRAE 62.1 Standards
Non-Wetting Absorption Distance
Visible steam plumes must fully absorb before reaching duct obstructions (elbows, filters, silencers) to prevent stagnant liquid pooling and biological mold growth:
Dabs ∝ (1 / Ntubes0.75) · vair · [ ΔRH / (100 − RH₂) ]0.65
Multi-Tube Rapid Dispersion Grids
Distributing steam across multiple vertical headers with engineered precision nozzles shortens absorption distance by up to 75% compared to single-wand injection.
Key Engineering Assumptions
- Atmospheric dry saturated steam at $100^\circ\text{C}$ ($h_{fg} = 2257\,\text{kJ/kg}$).
- Electric resistive or electrode boiler thermal efficiency $\eta \approx 95\%$.
- Isothermal humidification process along dry bulb lines.