💻 Microchannel Two-Phase Flow Boiling

Model high-heat-flux two-phase flow boiling in microchannels: two-phase HTC (htp), confinement number (Co), boiling number (Bo), chip wall temperature, and pressure drop.

⚡ Fortran 90 Engine Double Precision (IEEE 754) ✓ ISO / ASME Validated
📊 Solver Telemetry ● ACTIVE
👁️ Consultations 36
⚡ Calculs faits 29
💾 Téléchargements 271 📦 Code Fortran 10.8 KB
📅 Mise en service Jun 2026
⏱️ Latence < 1 ms
⚡ Outils & Rapports :
💾 Télécharger Fortran 90

💻 Silicon Microchannel Cold Plate & Confined Vapor Slugs

Real-time visual simulation: High-heat-flux microchannel array with Taylor vapor slugs sweeping through micro-fins

📝 Configuration & Presets

🖥️ AI GPU Chip (R1233zd) ⚡ EV SiC Inverter (Water) 📡 Radar GaN RF Power ❄️ Micro-Evaporator Loop
📐 Microchannel Array Dimensions
⚡ Operating Hydraulics & Heat Flux
1 W/cm² = 10 kW/m²
🧪 Fluid Thermophysical Properties
Kandlikar Microchannel Formulation:
• Confinement Number: Co = (1/Dh) √(σ / (g (ρL − ρV))) > 0.5
• Boiling Number: Bo = q″ / (G · hfg)
• Two-Phase HTC: htp = max( hNBD, hCBD ) [W/(m²·K)]
• Wall Temperature: Twall = Tsat + (q″ / htp) [°C]

📊 Microchannel Boiling Results

📊 Output Summary
💾 Fortran Source

Two-Phase Boiling HTC (htp)
htp = 80,098 W/(m²·K)
Base Wall Temp: 53.6 °C (Tsat = 38.6 °C) | Heat: 360.0 W
Co = 3.30 (Microchannel)
Hydraulic Diameter (Dh) 0.300 mm Microchannel regime
Boiling Number (Bo) 7.69e-3 q″ / (G · hfg)
Two-Phase Pressure Drop 8.55 kPa 0.086 bar
Liquid-Only HTC (hLO) 2,311 W/(m²·K) Boiling enhancement = 34.7x

📈 Boiling HTC h_tp [W/(m²·K)] vs Vapor Quality x

📉 Two-Phase Pressure Drop ΔP (kPa) vs Mass Flux G

=================================================================
 THERMOFLUIDCALC — MICROCHANNEL FLOW BOILING (KANDLIKAR) REPORT
=================================================================
Case Title                 : AI Server GPU Direct-to-Chip Microchannel Cold Plate
Microchannel Array         : w = 0.20 mm, h = 0.60 mm, L = 25.0 mm (Dh = 0.300 mm, N = 60)
Operating Flow Conditions  : Mass Flux G = 800.0 kg/(m2.s), Base Heat Flux q" = 120.0 W/cm2 (1200.0 kW/m2)
Thermodynamic State        : Vapor Quality x = 0.30, Saturation Pressure = 2.50 bar (Tsat = 38.6 C)
-----------------------------------------------------------------
CONFINEMENT NUMBER (Co)    : 3.304 [Confined Microchannel Flow]
BOILING NUMBER (Bo)        : 7.692e-3
TWO-PHASE BOILING HTC (htp): 80,097.6 W/(m2.K)
Liquid-Only Baseline HTC   : 2,311.5 W/(m2.K)
BASE WALL CHIP TEMPERATURE : 53.57 deg C (Overheat DeltaT = 14.98 C)
Two-Phase Pressure Drop    : 8.55 kPa (0.0855 bar)
Total Dissipated Heat Power: 360.00 W
=================================================================

📘 Calculation Methodology & Microchannel Boiling Standards

Kandlikar Microchannel Correlation

Incorporates confinement effects ($Co$) and boiling number ($Bo$) to capture transition between nucleate bubble nucleation and thin-film evaporation:

htp = max( hNBD, hCBD )

Confinement Number Criterion

When $Co = \frac{1}{D_h}\sqrt{\frac{\sigma}{g(\rho_L - \rho_V)}} > 0.5$, bubble growth is constrained by channel walls, forming elongated Taylor slugs.

Key Engineering Assumptions

  • Parallel rectangular microchannel heat sinks with uniform flow distribution.
  • Saturated two-phase flow boiling regimes ($0.05 \le x \le 0.85$).
  • Applicable to semiconductor electronics, high-power lasers, and compact heat exchangers.