🧍 Thermal Comfort (PMV & PPD)

Evaluate indoor thermal comfort based on Fanger's 6-parameter model (ISO 7730 / ASHRAE 55), computing Predicted Mean Vote and Predicted Percentage Dissatisfied.

⚡ Fortran 90 Engine Double Precision (IEEE 754) ✓ ISO / ASME Validated
📊 Solver Telemetry ● ACTIVE
👁️ Consultations 23
⚡ Calculs faits 21
💾 Téléchargements 150 📦 Code Fortran 4.4 KB
📅 Mise en service Jun 2026
⏱️ Latence < 1 ms
⚡ Outils & Rapports :
💾 Télécharger Fortran 90

🧍 Fanger Thermal Comfort Mannequin & 7-Point PMV Gauge

Real-time thermal radiation exchange, convective heat loss & ISO 7730 comfort zones

📝 Configuration & Presets

☀️ Summer Office (24.5°C / 0.5 clo) ❄️ Winter Office (21°C / 1.0 clo) 🛍️ Retail Active (1.7 met) 🌀 Ceiling Fan (0.8 m/s)
🌡️ Thermal Environmental Parameters
Surrounding surface temperatures
Still indoor air: 0.10 to 0.20 m/s
🏃 Occupant Activity & Clothing Insulation
Seated office: 1.0-1.2, Standing: 1.4-1.8
Summer: 0.5 clo, Winter: 1.0 clo
Fanger ISO 7730 Formulations:
• PMV = [0.303 · e−0.036 M + 0.028] · L [−3 to +3]
• PPD = 100 − 95 · exp(−0.03353 PMV⁴ − 0.2179 PMV²) [%]
• Cat A: |PMV| ≤ 0.2 (PPD ≤ 6%)
• Cat B: |PMV| ≤ 0.5 (PPD ≤ 10%)

📊 Thermal Comfort Results

📊 Output Summary
💾 Fortran Source

Predicted Mean Vote (PMV)
PMV = -0.40
✅ ISO 7730 Category B (PPD ≤ 10% — Normal Standard)
PPD = 8.3 %
Clothing Surface Temp (Tcl) 29.93 °C Skin Temp ~ 33.7 °C
Body Thermal Balance Load (L) -6.80 W/m² Heat Imbalance
Operative Temperature (Top) 24.8 °C ½ (Ta + Tr)
Metabolic Heat Rate 64.0 W/m² 1.10 met

📈 Predicted Mean Vote (PMV) vs Air Temperature

📉 Predicted Percentage of Dissatisfied (PPD) vs PMV

=================================================================
 THERMOFLUIDCALC — ISO 7730 / ASHRAE 55 THERMAL COMFORT REPORT
=================================================================
Case Title                 : Commercial Office Standard Summer Comfort
Air Temperature (Ta)       : 24.50 °C
Mean Radiant Temp (Tr)     : 25.00 °C
Relative Air Velocity      : 0.15 m/s (29.5 FPM)
Relative Humidity (RH)     : 50.0 %
Metabolic Activity Rate    : 1.10 met (64.0 W/m2)
Clothing Insulation (clo)  : 0.50 clo (0.077 m2.K/W)
-----------------------------------------------------------------
Clothing Surface Temp (Tcl): 29.93 °C
Thermal Imbalance Load (L) : -6.80 W/m2
PREDICTED MEAN VOTE (PMV)  : -0.397
PREDICTED DISSATISFIED PPD : 8.28 %
Comfort Classification     : ✅ ISO 7730 Category B (PPD ≤ 10% — Normal Standard)
=================================================================

📘 Calculation Methodology & ISO 7730 Standards

The Fanger 6-Parameter Model

Combines physiological skin heat loss, dry/latent respiration, radiative exchange with walls, and convective heat transfer to compute the net thermal load $L$:

PMV = [0.303 · e−0.036 M + 0.028] · L

ISO 7730 Comfort Categories

  • Category A: $-0.2 \le PMV \le +0.2$ ($PPD \le 6\%$) — Premium spaces.
  • Category B: $-0.5 \le PMV \le +0.5$ ($PPD \le 10\%$) — New commercial buildings.
  • Category C: $-0.7 \le PMV \le +0.7$ ($PPD \le 15\%$) — Existing buildings.

Key Engineering Assumptions

  • Steady-state human body thermal equilibrium.
  • External mechanical work $W = 0\,\text{W/m}^2$.
  • Uniform clothing distribution across body surface.