🖥️ Data Center PUE & Cooling
Compute Data Center Power Usage Effectiveness (PUE), DCiE, server rack CFM airflow demand per kW, and cold/hot aisle containment thermal metrics per ASHRAE TC 9.9.
⚡ Fortran 90 Engine
Double Precision (IEEE 754)
✓ ISO / ASME Validated
📊 Solver Telemetry
● ACTIVE
👁️ Consultations
37
⚡ Calculs faits
31
💾 Téléchargements
374
📦 Code Fortran
4.4 KB
📅 Mise en service
Jun 2026
⏱️ Latence
< 1 ms
🖥️ Data Center Server Rack Cold/Hot Aisle Thermal Airflow
Real-time visual simulation of perforated floor tile cold supply & hot exhaust ceiling return📝 Configuration & Presets
☁️ Hyperscale CAC (PUE 1.18)
🏢 Enterprise HAC (PUE 1.42)
🏛️ Legacy Open Aisle (PUE 1.87)
⚡ 2.5 MW AI GPU Cluster
The Green Grid & ASHRAE TC 9.9 Formulations:
• PUE = Ptotal / PIT (DCiE = 1 / PUE × 100%)
• Airflow: CFM = (1756 · PIT,kW) / ΔTrack,°C
• Volumetric Flow: Q = CFM × 1.699 [m³/h]
• Return Air Index: RAI = (Treturn − Tsupply) / (Track,out − Tsupply)
• PUE = Ptotal / PIT (DCiE = 1 / PUE × 100%)
• Airflow: CFM = (1756 · PIT,kW) / ΔTrack,°C
• Volumetric Flow: Q = CFM × 1.699 [m³/h]
• Return Air Index: RAI = (Treturn − Tsupply) / (Track,out − Tsupply)
📊 Efficiency & Airflow Results
📊 Output Summary
Power Usage Effectiveness (PUE)
PUE = 1.867
🚨 Low Efficiency / High Overhead (PUE > 1.75)
DCiE = 53.6 %
Required Total Airflow
58,533 CFM
99,448 m³/h
Total Facility Power Draw
560 kW
IT: 300 kW + Overhead: 260 kW
Specific Airflow Demand
195.1 CFM/kW
ΔTrack = 9.0 °C
Return Air Index (RAI)
65 %
Open Aisle
📈 PUE vs Cooling Infrastructure Power (kW)
📉 Required Airflow (CFM) vs Server Delta T
================================================================= THERMOFLUIDCALC — DATA CENTER PUE & COOLING REPORT ================================================================= Case Title : Legacy Raised Floor Uncontained Data Center (PUE ~ 1.85) IT Server Equipment Power : 300.0 kW (53.6 %) Cooling Infrastructure : 210.0 kW (37.5 %) UPS & Transformer Losses : 40.0 kW Lighting & Aux Power : 10.0 kW TOTAL FACILITY POWER : 560.0 kW ----------------------------------------------------------------- POWER USAGE EFFECTIVENESS : 1.867 DCiE Efficiency Metric : 53.57 % Energy Efficiency Rating : 🚨 Low Efficiency / High Overhead (PUE > 1.75) Cold / Hot Aisle Temp : 18.0 °C / 27.0 °C (ΔT = 9.0 °C) Required Facility Airflow : 58,533 CFM (99,448 m3/h) Specific Airflow Demand : 195.1 CFM/kW Return Air Index (RAI) : 65.0 % =================================================================
📘 Calculation Methodology & ASHRAE TC 9.9 Standards
Power Usage Effectiveness (PUE)
The global standard benchmark metric defined by The Green Grid comparing total building facility power to IT mission-critical computing load:
PUE = Ptotal / PIT = 1 + (Poverhead / PIT)
Aisle Containment & Airflow Balance
Containment eliminates hot air recirculation and cold air bypass, allowing supply air temperatures to rise to $24^\circ\text{C}-27^\circ\text{C}$ to maximize chiller free cooling.
Key Engineering Assumptions
- Air density $\rho = 1.18\,\text{kg/m}^3$ at data hall operating elevations.
- Specific heat of air $c_p = 1.006\,\text{kJ/(kg·K)}$.
- ASHRAE TC 9.9 thermal envelope A1/A2 recommended operating ranges.