❄️ Psychrometric Cooling & Dehumidification Coil Process Line
Real-time visual psychrometric state points: Entering (1) → Leaving (2) → Apparatus Dew Point (ADP)📝 Configuration & Presets
🏢 Office Comfort (28°C / 55%)
🌴 Tropical Monsoon (34°C / 80%)
🖥️ Data Center (SHR > 0.95)
🏥 Hospital Operating Suite
Psychrometric Formulations:
• Leaving DB: Tdb2 = ADP + BF · (Tdb1 − ADP)
• Total Capacity: Qtotal = ṁa · (h₁ − h₂) [kW]
• Sensible Ratio: SHR = Qsens / Qtotal
• Condensate Rate: ṁw = ṁa · (w₁ − w₂) × 3600 [L/h]
• Leaving DB: Tdb2 = ADP + BF · (Tdb1 − ADP)
• Total Capacity: Qtotal = ṁa · (h₁ − h₂) [kW]
• Sensible Ratio: SHR = Qsens / Qtotal
• Condensate Rate: ṁw = ṁa · (w₁ − w₂) × 3600 [L/h]
📊 Coil Performance Results
📊 Output Summary
Total Cooling Coil Load
Qtotal = 33.08 kW (9.4 TR)
Leaving Air State: 7.5 °C DB @ 97.8 % RH
SHR = 0.568
Sensible Capacity (Qs)
18.77 kW
56.8 % of Total
Latent Dehumidification (Ql)
14.30 kW
43.2 % Latent
Condensate Extraction Rate
19.92 L/h
Δw = 4.88 g/kg
Chilled Water Flow (ΔT=5.5°C)
5.18 m³/h
22.8 GPM
📈 Total Cooling Capacity (kW) vs Air Flow Q
📉 Condensate Extraction Rate (L/h) vs ADP
================================================================= THERMOFLUIDCALC — COOLING COIL PSYCHROMETRIC REPORT ================================================================= Case Title : Hospital Surgical Suite 100% Fresh Air AHU Entering Air State (1) : 24.0 °C DB, 60.0 % RH (h=52.62 kJ/kg, w=11.19 g/kg) Apparatus Dew Point (ADP) : 6.50 °C Coil Bypass Factor (BF) : 0.060 (Contact Factor = 0.940) Air Volume Flow Rate : 3,500.0 m3/h (2,060 CFM) ----------------------------------------------------------------- Leaving Air State (2) : 7.5 °C DB, 97.8 % RH (h=23.47 kJ/kg, w=6.31 g/kg) TOTAL COOLING CAPACITY : 33.08 kW (9.41 TR, 112866 BTU/h) Sensible Capacity (Qs) : 18.77 kW (56.8 %) Latent Capacity (Ql) : 14.30 kW (43.2 %) Sensible Heat Ratio (SHR) : 0.5676 Condensate Moisture Rate : 19.92 L/h (19.92 kg/h) Chilled Water Flow (dT=5.5°C): 5.18 m3/h (22.8 GPM) =================================================================
📘 Calculation Methodology & ASHRAE Standards
Apparatus Dew Point & Bypass Factor
The portion of air that passes untouched through fin spaces is represented by the Bypass Factor $BF$. The condition curve connects state 1 directly toward $ADP$:
Tdb2 = ADP + BF · (Tdb1 − ADP)
Sensible Heat Ratio & Dehumidification
When the coil surface temperature $ADP < T_{dew1}$, simultaneous cooling and moisture condensation occur. Deeper 6–8 row coils achieve $BF \le 0.08$ for deep moisture removal.
Key Engineering Assumptions
- Standard atmospheric pressure $P = 101.325\,\text{kPa}$.
- Ideal gas mixture thermodynamics for dry air and water vapor.
- Chilled water specific heat $c_p = 4.186\,\text{kJ/(kg·K)}$.