🚪 Air Curtain Aerodynamics
Determine air curtain Foster Deflection Number (Dn), AMCA 220 aerodynamic sealing efficiency, doorway infiltration reduction, and heating/cooling energy saved.
⚡ Fortran 90 Engine
Double Precision (IEEE 754)
✓ ISO / ASME Validated
📊 Solver Telemetry
● ACTIVE
👁️ Consultations
43
⚡ Calculs faits
34
💾 Téléchargements
213
📦 Code Fortran
4.4 KB
📅 Mise en service
Jun 2026
⏱️ Latence
< 1 ms
🚪 Overhead Air Curtain Planar Jet Barrier & Deflection
Real-time visual simulation of downward turbulent jet resisting outdoor thermal & wind infiltration📝 Configuration & Presets
🛒 Supermarket (H=2.8m, 11.5 m/s)
❄️ Cold Storage (-20°C / +20°C)
🚛 Loading Dock (H=4.5m, 20 m/s)
🛍️ Retail Quiet (8.5 m/s)
AMCA 220 Formulations:
• Deflection Number: Dn = (ρi b₀ v₀² cos α) / [ g H² |ρo − ρi| + ½ Cp ρo vw² H ]
• Sealing Efficiency: Eseal ≈ 70% to 85% in optimal range (0.15 ≤ Dn ≤ 0.40)
• Thermal Energy Saved: Qsaved = Eseal · ṁinfilt · cp · |Ti − To| [kW]
• Deflection Number: Dn = (ρi b₀ v₀² cos α) / [ g H² |ρo − ρi| + ½ Cp ρo vw² H ]
• Sealing Efficiency: Eseal ≈ 70% to 85% in optimal range (0.15 ≤ Dn ≤ 0.40)
• Thermal Energy Saved: Qsaved = Eseal · ṁinfilt · cp · |Ti − To| [kW]
📊 Air Curtain Performance Results
📊 Output Summary
Aerodynamic Sealing Efficiency
Eseal = 75.0 %
⚠️ OVERPOWERED (Excessive Jet Spill & Turbulence)
Dn = 0.625
Thermal Energy Saved
52.80 kW
180176 BTU/h
Unprotected Infiltration
10,337 m³/h
6,084 CFM
Fan Electric Power Draw
0.15 kW
COPbarrier = 350.7
Air Curtain Discharge Flow
4,099 m³/h
2.2m wide × 45mm
📈 Sealing Efficiency (%) vs Discharge Velocity
📉 Heating/Cooling Energy Saved (kW) vs Outdoor Temp
================================================================= THERMOFLUIDCALC — AIR CURTAIN AERODYNAMICS REPORT ================================================================= Case Title : Commercial Supermarket Entrance Air Curtain Doorway Dimensions (H x W) : 2.80 m x 2.20 m Nozzle Slot / Velocity : 45.0 mm / 11.50 m/s (Angle = 15.0°) Indoor / Outdoor Temp : 21.0 °C / 2.0 °C (ΔT = 19.0 °C) Outdoor Cross Wind Speed : 2.00 m/s ----------------------------------------------------------------- Foster Deflection No (Dn) : 0.6248 Aerodynamic Barrier Status : ⚠️ OVERPOWERED (Excessive Jet Spill & Turbulence) SEALING EFFICIENCY (E_seal): 75.00 % Unprotected Infiltration : 10,336.7 m3/h (6,084 CFM) Thermal Energy Saved : 52.80 kW (180176 BTU/h) Fan Power Consumption : 0.15 kW (COP = 350.7) =================================================================
📘 Calculation Methodology & AMCA 220 Standards
Foster Deflection Criterion
The Deflection Number $D_n$ compares the downward planar jet momentum against the opposing transverse forces of thermal buoyancy and wind pressure:
Dn = (ρi b₀ v₀² cos α) / [ g H² Δρ + ½ Cp ρo vw² H ]
Optimal Barrier Operation
When $0.15 \le D_n \le 0.40$, the air curtain reaches the floor with sufficient momentum to split cleanly, preventing up to 85% of conditioned air loss.
Key Engineering Assumptions
- Standard planar turbulent turbulent jet expansion angle $\approx 14^\circ$.
- Fan combined motor and aerodynamic efficiency $\eta = 60\%$.
- Outward nozzle discharge angle $\alpha = 15^\circ$ to counteract inward draft.