🌊 Cooling Tower Merkel Integral (KaV/L)
Calculate cooling tower mass transfer demand (Merkel number KaV/L) via Chebyshev 4-point quadrature, thermal effectiveness, range, approach, and evaporation loss.
⚡ Fortran 90 Engine
Double Precision (IEEE 754)
✓ ISO / ASME Validated
📊 Solver Telemetry
● ACTIVE
👁️ Consultations
31
⚡ Calculs faits
28
💾 Téléchargements
374
📦 Code Fortran
6.4 KB
📅 Mise en service
Jun 2026
⏱️ Latence
< 1 ms
🌊 Induced Draft Counter-Flow Cooling Tower & Film Packing Simulation
Real-time visual simulation of hot water spray, evaporative mass transfer & upward air drafting📝 Configuration & Presets
CTI Merkel Formulations:
• Merkel Integral: KaV / L = ∫ [ cw dTw / (hsat − ha) ]
• Range = Tw,in − Tw,out | Approach = Tw,out − Twb
• Thermal Effectiveness: η = Range / (Tw,in − Twb) × 100%
• Evaporation Loss: Qevap ≈ 0.0018 · L · Range [m³/h]
• Merkel Integral: KaV / L = ∫ [ cw dTw / (hsat − ha) ]
• Range = Tw,in − Tw,out | Approach = Tw,out − Twb
• Thermal Effectiveness: η = Range / (Tw,in − Twb) × 100%
• Evaporation Loss: Qevap ≈ 0.0018 · L · Range [m³/h]
📊 Merkel Analysis Results
📊 Output Summary
Tower Characteristic / Merkel Number
KaV / L = 2.874
Thermal Effectiveness: 66.7 % (Range = 12.0 °C, Approach = 6.0 °C)
L/G = 1.30
Evaporation Water Loss
8.64 m³/h
2.16 % of circulation
Fan Air Flow Demand
260,235 m³/h
153,169 CFM
Thermal Cooling Heat Rejected
5,570 kW
1,584 Tons
Approach to Wet Bulb
6.0 °C
Twb = 18.0 °C
📈 Merkel Number (KaV/L) vs Liquid-to-Gas Ratio (L/G)
📉 Thermal Effectiveness (%) vs Approach to Wet Bulb (°C)
================================================================= THERMOFLUIDCALC — COOLING TOWER MERKEL INTEGRAL REPORT ================================================================= Case Title : Arid Desert Climate High-Range Cooling Tower Water Flow Rate (L) : 400.0 m3/h (1761.2 GPM) Water Temperatures In/Out : 36.0 °C / 24.0 °C (Range = 12.0 °C) Ambient Air Dry/Wet Bulb : 38.0 °C / 18.0 °C (Approach = 6.0 °C) Liquid-to-Gas Ratio (L/G) : 1.300 ----------------------------------------------------------------- MERKEL NUMBER (KaV / L) : 2.8741 (Chebyshev 4-pt Quadrature) Thermal Effectiveness : 66.67 % Heat Rejected : 5,570.2 kW (1,584 TR) Evaporative Water Loss : 8.64 m3/h (38.0 GPM) Required Airflow : 260,235 m3/h (153,169 CFM) =================================================================
📘 Calculation Methodology & CTI Standards
Merkel Enthalpy Driving Force
The Merkel theory unifies sensible and latent heat transfer into a single potential: the enthalpy difference between saturated air at the water interface and bulk moist air:
KaV/L = ∫ [ cw dTw / (hsat − ha) ]
Chebyshev 4-Point Quadrature
CTI Bulletin P-130 specifies evaluation at 4 standard points across the cooling range ($10\%, 40\%, 60\%, 90\%$) for high numerical accuracy without manual graphical integration.
Key Engineering Assumptions
- Lewis factor $Le_f = 1.0$ (equal mass and heat transfer boundary layers).
- Negligible reduction in water flow rate along the tower fill.
- Saturated air at water temperature interface.