๐ Cooling Tower Merkel Integral (KaV/L)
Calculate cooling tower mass transfer demand (Merkel number KaV/L) via Chebyshev 4-point quadrature, thermal effectiveness, range, approach, and evaporation loss.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
31
โก Solves
28
๐พ Downloads
497
๐ฆ Fortran Code
6.4 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
๐ Induced Draft Counter-Flow Cooling Tower & Film Packing Simulation
Real-time visual simulation of hot water spray, evaporative mass transfer & upward air drafting๐ Configuration & Presets
๐ญ Industrial (37ยฐC โ 29ยฐC)
โก Power Plant (3500 mยณ/h)
๐ข HVAC Chiller Loop
โ๏ธ Desert Arid Climate
CTI Merkel Formulations:
โข Merkel Integral: KaV / L = โซ [ cw dTw / (hsat โ ha) ]
โข Range = Tw,in โ Tw,out | Approach = Tw,out โ Twb
โข Thermal Effectiveness: ฮท = Range / (Tw,in โ Twb) ร 100%
โข Evaporation Loss: Qevap โ 0.0018 ยท L ยท Range [mยณ/h]
โข Merkel Integral: KaV / L = โซ [ cw dTw / (hsat โ ha) ]
โข Range = Tw,in โ Tw,out | Approach = Tw,out โ Twb
โข Thermal Effectiveness: ฮท = Range / (Tw,in โ Twb) ร 100%
โข Evaporation Loss: Qevap โ 0.0018 ยท L ยท Range [mยณ/h]
๐ Merkel Analysis Results
๐ Output Summary
Tower Characteristic / Merkel Number
KaV / L = 2.874
Thermal Effectiveness: 66.7 % (Range = 12.0 ยฐC, Approach = 6.0 ยฐC)
L/G = 1.30
Evaporation Water Loss
8.64 mยณ/h
2.16 % of circulation
Fan Air Flow Demand
260,235 mยณ/h
153,169 CFM
Thermal Cooling Heat Rejected
5,570 kW
1,584 Tons
Approach to Wet Bulb
6.0 ยฐC
Twb = 18.0 ยฐC
๐ Merkel Number (KaV/L) vs Liquid-to-Gas Ratio (L/G)
๐ Thermal Effectiveness (%) vs Approach to Wet Bulb (ยฐC)
================================================================= THERMOFLUIDCALC โ COOLING TOWER MERKEL INTEGRAL REPORT ================================================================= Case Title : Arid Desert Climate High-Range Cooling Tower Water Flow Rate (L) : 400.0 m3/h (1761.2 GPM) Water Temperatures In/Out : 36.0 ยฐC / 24.0 ยฐC (Range = 12.0 ยฐC) Ambient Air Dry/Wet Bulb : 38.0 ยฐC / 18.0 ยฐC (Approach = 6.0 ยฐC) Liquid-to-Gas Ratio (L/G) : 1.300 ----------------------------------------------------------------- MERKEL NUMBER (KaV / L) : 2.8741 (Chebyshev 4-pt Quadrature) Thermal Effectiveness : 66.67 % Heat Rejected : 5,570.2 kW (1,584 TR) Evaporative Water Loss : 8.64 m3/h (38.0 GPM) Required Airflow : 260,235 m3/h (153,169 CFM) =================================================================
๐ Calculation Methodology & CTI Standards
Merkel Enthalpy Driving Force
The Merkel theory unifies sensible and latent heat transfer into a single potential: the enthalpy difference between saturated air at the water interface and bulk moist air:
KaV/L = โซ [ cw dTw / (hsat โ ha) ]
Chebyshev 4-Point Quadrature
CTI Bulletin P-130 specifies evaluation at 4 standard points across the cooling range ($10\%, 40\%, 60\%, 90\%$) for high numerical accuracy without manual graphical integration.
Key Engineering Assumptions
- Lewis factor $Le_f = 1.0$ (equal mass and heat transfer boundary layers).
- Negligible reduction in water flow rate along the tower fill.
- Saturated air at water temperature interface.