โก Supercritical CO2 Brazed Plate Exchanger (BPHE)
Size Supercritical CO2 (sCO2) Brazed Plate Heat Exchangers (BPHE): pseudo-critical temperature (Tpc), Jackson & Hall chevron Nusselt model, compactness density, and gas cooler duty.
โก Fortran 90 Engine
Double Precision (IEEE 754)
โ ISO / ASME Validated
๐ Solver Telemetry
โ ACTIVE
๐๏ธ Views
42
โก Solves
36
๐พ Downloads
352
๐ฆ Fortran Code
4.1 KB
๐
Released
Jun 2026
โฑ๏ธ Latency
< 1 ms
โก Supercritical CO2 High-Pressure Chevron Corrugated Channels
Real-time visual simulation: sCO2 gas cooler channel (red to orange) and counterflow water (blue to cyan)๐ Configuration & Presets
๐ฅ Transcritical CO2 Heat Pump
โก sCO2 Brayton Recuperator
๐ R744 Supermarket Gas Cooler
๐ญ sCO2 Waste Heat Recovery
Supercritical CO2 BPHE Formulation:
โข Pseudo-Critical Temp: Tpc = 31.04 + 0.35 ยท (P โ 73.8) [ยฐC]
โข Supercritical Chevron Nusselt: Nu = 0.30 ยท Re0.68 ยท Pr0.40 ยท sin(ฮฒ)0.30
โข Thermal Compactness: βvol > 1000 mยฒ/mยณ (Ultra-compact footprint)
โข Heat Duty: Qฬ = แนsCO2 ยท (hin โ hout) [kW].
โข Pseudo-Critical Temp: Tpc = 31.04 + 0.35 ยท (P โ 73.8) [ยฐC]
โข Supercritical Chevron Nusselt: Nu = 0.30 ยท Re0.68 ยท Pr0.40 ยท sin(ฮฒ)0.30
โข Thermal Compactness: βvol > 1000 mยฒ/mยณ (Ultra-compact footprint)
โข Heat Duty: Qฬ = แนsCO2 ยท (hin โ hout) [kW].
๐ Performance Results
๐ Output Summary
Gas Cooler Thermal Duty (Qฬ)
241.1 kW (0.241 MW)
Pseudo-Critical Tpc: 35.0 ยฐC | Pressure: 85 bar
TRANS-PSEUDOCRITICAL COOLING
sCO2 Outlet Temperature
33.8 ยฐC
Inlet = 95 ยฐC
Coolant Water Outlet Temp
38.0 ยฐC
Inlet = 15 ยฐC
sCO2 Heat Transfer Coeff (h)
3482 W/(mยฒยทK)
Overall U = 2024 W/(mยฒยทK)
Area Compactness Density
400 mยฒ/mยณ
40 chevron plates
๐ Heat Duty Qฬ (kW) vs Operating Pressure P (bar)
๐ sCO2 Heat Coeff hs [W/(mยฒยทK)] vs Plates Count Np
================================================================= THERMOFLUIDCALC โ SUPERCRITICAL CO2 BPHE SIZING REPORT ================================================================= Case Title : Supermarket R744 Refrigeration Gas Cooler BPHE Supercritical CO2 Stream : P = 85.0 bar, T_in = 95.0 C, m = 1.20 kg/s (Tpc = 34.96 C) Coolant Water Stream : T_cool_in = 15.0 C, m_cool = 2.50 kg/s BPHE Plate Geometry : Np = 40 plates, W = 0.20 m, L = 0.50 m, Chevron = 45 deg ----------------------------------------------------------------- SUPERCRITICAL REGIME : TRANS-PSEUDOCRITICAL COOLING GAS COOLER THERMAL DUTY (Q): 241.09 kW (0.241 MW) sCO2 Heat Coeff (h_sco2) : 3481.6 W/(m2.K) Overall Heat Transfer (U) : 2024.1 W/(m2.K) sCO2 Outlet Temperature : 33.80 deg C Coolant Water Outlet Temp : 38.05 deg C sCO2 Pressure Drop : 2.44 kPa Area Compactness Density : 400 m2/m3 =================================================================
๐ Calculation Methodology & Supercritical CO2 Standards
Pseudo-Critical Property Variations
Near the pseudo-critical line ($T_{pc}$), $CO_2$ undergoes dramatic non-linear spikes in specific heat ($c_p$) and shifts in density, providing exceptionally high heat exchange rates without boiling/pinch limitations.
High-Pressure Brazed Plate Compactness
Chevron corrugated vacuum-brazed stainless steel plates provide compactness exceeding $1000\,\text{m}^2/\text{m}^3$ while withstanding pressures beyond $100 - 150\,\text{bar}$.
Key Engineering Assumptions
- Modified Jackson & Hall supercritical Nusselt correlation for chevron BPHEs.
- Counter-current gas cooling without condensation phase change.
- Used in transcritical $CO_2$ heat pumps, R744 supermarket refrigeration, and $sCO_2$ Brayton power cycles.